Site Offices & Welfare Areas

Electrical requirements for temporary site offices, welfare facilities, canteens, drying rooms, and accommodation units on UAE construction sites.

Applicable Standards

Temporary site offices and welfare facilities are classified as temporary electrical installations under Section 9.6 of the Abu Dhabi DoE EWR 2020 and the equivalent section of the Dubai Building Code 2021. They must comply with all the requirements for temporary installations, including RCD protection, earthing, and periodic inspection. Where welfare facilities are provided for more than 50 workers, they are also subject to MoHRE labour accommodation standards.

  • Classification

    Temporary electrical installation — DoE EWR 2020 Section 9.6

    critical
  • RCD protection

    All socket outlet and lighting circuits — ≤30 mA RCD

    critical
  • Earthing

    TN-S or TT earthing — bonding of all metal structures

    critical
  • Periodic inspection

    Monthly (ADOSH-SF CoP 15.0)

    critical

Lighting Requirements

Minimum illuminance levels in temporary site offices and welfare areas are specified in ADOSH-SF CoP 15.0 and the UAE Labour Camp Regulations (Cabinet Resolution No. 13 of 2009 for accommodation). Emergency lighting with battery backup is mandatory in all occupied temporary buildings.

  • General office areas

    Minimum 300 lux at desk level

    standard
  • Welfare / rest areas

    Minimum 100 lux

    standard
  • Toilet / ablution areas

    Minimum 100 lux

    standard
  • Canteen / kitchen

    Minimum 200 lux at work surfaces

    standard
  • Emergency lighting

    Battery backup — minimum 1 hour duration — all escape routes

    critical
  • Emergency lighting test

    Monthly function test — 6-monthly full duration test

    critical

Kitchen and Canteen Electrical Safety

Canteen and kitchen areas in temporary welfare facilities present specific electrical hazards due to the combination of water, heat, and high-power equipment. All socket outlets in kitchen areas must be protected by 30 mA RCDs. Fixed cooking equipment must be on dedicated circuits with local isolation. Gas detection systems must be electrically safe (intrinsically safe or explosion-proof) where LPG is used.

  • Socket outlets in kitchen

    30 mA RCD protected — Type A minimum

    critical
  • Fixed cooking equipment

    Dedicated circuit with local lockable isolator

    critical
  • IP rating in wet areas

    Minimum IP44 for all fittings within 2.4 m of water sources

    critical
  • Gas detection (LPG)

    Intrinsically safe or Ex-rated electrical equipment in LPG zones

    critical
  • Supplementary bonding

    All metal sinks, worktops, and appliances bonded to earth

    critical

Air Conditioning Units

Air conditioning is mandatory in all UAE site offices and welfare areas. AC units must be on dedicated circuits with local isolation. Outdoor condensing units must be properly earthed and protected from physical damage. Drain lines must not create water ingress hazards near electrical equipment.

  • Dedicated circuit

    Each AC unit on its own circuit with local isolator

    critical
  • Outdoor unit earthing

    Condensing unit frame bonded to earth

    critical
  • Circuit protection

    MCB rated per manufacturer specification + RCD protection

    critical
  • Drain line routing

    Must not discharge near electrical equipment or DBs

    standard