RCDs (Residual Current Devices)

RCD types, trip current ratings, installation requirements, and testing obligations for UAE construction sites, site offices, and welfare facilities.

Mandatory RCD Protection

Residual Current Devices (RCDs) are mandatory on all UAE construction site electrical installations. The Abu Dhabi DoE EWR 2020 (Section 9.5) and the Dubai Building Code 2021 both require RCD protection on all socket outlet circuits, portable equipment circuits, and outdoor circuits on construction sites. ADOSH-SF CoP 15.0 reinforces this requirement as a critical control measure against electric shock fatalities.

  • Socket outlet circuits

    RCD ≤30 mA — mandatory on all circuits

    critical
  • Portable equipment circuits

    RCD ≤30 mA — mandatory

    critical
  • Outdoor circuits

    RCD ≤30 mA — mandatory

    critical
  • Lighting circuits (site)

    RCD ≤30 mA — mandatory

    critical
  • Fixed equipment (>32A)

    RCD ≤100 mA or 300 mA (fire protection)

    standard
  • TT earthing system

    RCD mandatory on ALL circuits

    critical

RCD Types and Selection

The correct RCD type must be selected based on the load. Type AC RCDs respond to sinusoidal AC residual currents only. Type A RCDs respond to AC and pulsating DC residual currents (required for circuits with electronic equipment, VSDs, and IT equipment). Type B RCDs respond to AC, pulsating DC, and smooth DC (required for circuits supplying frequency inverters and EV chargers). On UAE construction sites with significant electronic equipment, Type A RCDs are the minimum requirement.

RCD TypeDetectsTypical ApplicationUAE Requirement
Type ACSinusoidal AC onlySimple resistive/inductive loadsMinimum for basic lighting circuits
Type AAC + pulsating DCElectronic equipment, power tools, computersMinimum for site offices and welfare areas
Type BAC + pulsating DC + smooth DCVSDs, EV chargers, solar invertersRequired for generator AVR circuits, VSDs
Type S (selective)AC — time-delayedMain incoming RCD (discrimination)Required at main DB for discrimination

RCD Testing Requirements

RCDs must be tested at regular intervals to ensure they operate correctly. The test button on an RCD only confirms the mechanical operation — it does not verify the trip current or trip time. Proper testing requires an RCD tester that applies a known residual current and measures the trip time.

  • Test button check

    Monthly minimum — press test button, confirm trip

    critical
  • Instrument test (trip time)

    At commissioning and every 6 months — RCD tester required

    critical
  • Trip time — 30 mA RCD

    Must trip within 40 ms at rated current (IEC 61008)

    critical
  • Trip time — 100 mA RCD

    Must trip within 200 ms at rated current

    standard
  • Test records

    Written records of all RCD tests retained on site

    critical
  • Failed RCD

    Replace immediately — do not continue using a failed RCD

    critical

ADOSH-SF CoP 15.0 requires that RCD test records are available for inspection by the authority at any time. A failed RCD that has not been replaced is a prosecutable offence under UAE OSH law.