Site Safety UAE homepage logo — circular eagle badge with a maple leaf in the eye and red and green halvesSite Safety UAE
Login
Earthing, bonding & lightning protection

Earth pits, copper rods and the connection into the building — done safely and accepted first time

Drilling the pit is the visible part. The failures happen elsewhere: a service struck during augering, a connection backfilled before anyone witnessed it, a bonding schedule that never covered the lift rails or the chilled-water pipework, a resistance value copied from another project, and a lightning protection earth left isolated from the electrical earth. This is the full chain for villas, townhouses, commercial buildings, towers and industrial plots.

Version 1.0 · Last updated 2026-08-22 · Operating guidance only — confirm the current edition of the supply authority's electrical installation regulations, the building code and the fire and life safety code for your emirate before issue.

Delivery sequence

Seven stages, each with a hold point

The order is deliberate. Design and resistivity come before the bore, utility clearance before the auger turns, and the witnessed connection before backfill. Skipping a hold point almost always ends in re-excavation or a rejected energisation request.

1Design and soil resistivity survey

Earth electrode arrangement is a design output, not a site decision. A Wenner four-pin soil resistivity survey establishes whether rods, a rod array, a ring/foundation earth or an enhanced (backfill compound / deep-bore) electrode is needed. UAE sandy and saline soils vary enormously between coastal and inland plots, so a resistivity assumption copied from another project is the most common root cause of a failed acceptance test.

Hold point

Consultant-approved earthing layout, electrode schedule and acceptance value issued as IFC before any bore is set out.

2Utility clearance and permit

Every earth bore is an excavation into unverified ground. Obtain the utility drawings and NOCs (DEWA/ADDC/AADC/SEWA/EtihadWE, Etisalat/du, gas, district cooling, irrigation, drainage), scan and mark with CAT/genny or GPR, and hand-dig or vacuum-excavate a trial pit through the top service zone before mechanical augering.

Hold point

Excavation/ground-disturbance permit plus utility NOC references recorded on the PTW; no mechanical drilling inside a utility owner's tolerance zone until positively proved.

3Bore forming and electrode installation

Auger or drive the electrode to design depth. Sectional rods are coupled with the correct couplers and driving studs — never hammered directly onto a threaded end. Nobody enters the bore. Open bores are covered or rigidly barricaded whenever drilling stops.

Hold point

Pre-start plant and attachment check signed; exclusion zone set at maximum boom/attachment reach plus margin.

4Connection, inspection pit and backfill

Earth conductor is connected to the electrode by exothermic weld or an approved clamp inside an accessible inspection pit with a removable, labelled cover. The connection must remain inspectable and disconnectable for testing. Enhancement compound (bentonite / low-resistance backfill) is placed per the manufacturer's instructions, not improvised with salt or charcoal, which corrodes copper and pollutes groundwater.

Hold point

Consultant/authority inspection of the connection and pit before backfill — a covered connection that was never witnessed will be re-excavated.

5Main earthing terminal and protective bonding

The electrode conductor lands on the main earthing terminal (MET) in the meter/main LV room. Every extraneous-conductive-part is then bonded back to the MET: incoming water, fire and irrigation pipework, gas, HVAC/chilled-water and district cooling pipework, lift guide rails and machine room steel, structural steel and rebar where designated, PV array frames and DC containment, EV charger enclosures, pool and water-feature bonding, satellite/telecom and CCTV earths, and the LPS earth where a common earthing system is designed.

Hold point

Bonding schedule signed off against the approved drawing; every bond labelled 'Safety Electrical Connection — Do Not Remove'.

6Testing and verification

Earth electrode resistance (fall-of-potential or clamp method), continuity of protective and bonding conductors, insulation resistance, earth fault loop impedance (Ze and Zs), prospective fault current, RCD operation, and LPS down-conductor continuity where applicable. Tests are done by an authorised competent person with calibrated instruments and recorded on the utility's own test/inspection format.

Hold point

Calibration certificates attached; results recorded against the approved acceptance value before energisation is requested.

7Authority inspection, energisation and handover

The supply authority (or its approved inspection body) witnesses and energises. Handover includes the as-built earthing layout, pit locations and covers, test certificates, and the periodic re-test interval written into the O&M manual and the FM planned-maintenance system.

Hold point

No permanent load connected to a temporary earth arrangement; temporary construction earthing is formally removed and recorded when the permanent system takes over.

By building type

Villa, townhouse, commercial, tower, industrial and temporary supply

The physics is the same; the arrangement, the bonding scope and the inspection route are not. Use the row that matches the asset, then confirm against the approved electrical design.

Standalone villa

Earthing arrangement: TT or TN-C-S depending on the supply authority's policy for the district; RCD protection on all final circuits.

Electrode: Earth pit with one or more copper-bonded rods, or a deep-bore rod where surface resistivity is poor. Pit located in soft landscape, accessible, clear of driveways and future extensions.

Bonding scope: Main bonding of incoming water, gas (where present), HVAC pipework and metal structure; supplementary bonding in bathrooms per IEC 60364-7-701; separate bonding for pool, water feature and irrigation controllers.

Lightning protection: Risk assessment to IEC 62305-2 — many low-rise villas are exempt, but a rooftop PV array, tall palms/masts or an isolated plot can change the outcome. Where PV is installed, DC and AC surge protection plus array frame bonding is expected.

Authority step: Utility internal-wiring inspection and meter energisation; consultant sign-off of the earthing test record.

Townhouse / cluster development

Earthing arrangement: Common LV distribution from a district substation, individual metering per unit, shared main earthing arrangement per block.

Electrode: Earth pit array per substation/block with an interconnected earthing network; individual unit METs bonded back to the block earth rather than each unit driving its own isolated rod.

Bonding scope: Block-level bonding of risers, water pumps, boosters, gas manifolds, common-area lighting columns, gates and barriers, plus each unit's internal bonding.

Lightning protection: Usually assessed at block level. Common-area masts, lighting columns and roof plant are the trigger, not the individual dwelling.

Authority step: Substation earthing test and utility acceptance before the block is energised; developer/master-developer NOC where the plot sits inside a managed community.

Commercial, retail and offices

Earthing arrangement: TN-S from a dedicated substation; separate clean/technical earth for IT and BMS where designed, referenced to the same MET.

Electrode: Earth pit array or ring earth around the substation and building perimeter; foundation (rebar) earthing where designed and continuity-tested during construction.

Bonding scope: Structural steel, rebar mesh, curtain-wall framing, lift rails and machine rooms, escalators, chilled-water and district cooling pipework, generator and UPS earths, data-centre earthing bar, kitchen equipment, signage and façade lighting.

Lightning protection: IEC 62305 LPS is normally required. Air termination, down conductors on defined spacing, test joints, and an LPS earth that is bonded to the electrical earth to avoid dangerous potential difference.

Authority step: Utility inspection, Civil Defence inspection covering bonding/earthing of fire systems, and consultant/third-party verification before occupancy certificate.

High-rise and mixed-use towers

Earthing arrangement: TN-S with multiple LV rooms, earthing risers on each floor and floor-level earth bars.

Electrode: Foundation/pile earthing plus a perimeter ring and inspection pits; deep electrodes where the pile cap cannot be relied on.

Bonding scope: Vertical earth riser bonded at every floor to structural steel/rebar, riser ducts, firefighting pipework, lift shafts, façade access equipment (BMU) rails, telecom and antenna masts, and roof plant.

Lightning protection: Mandatory in practice. Down conductors integrated with structural steel where the structure is used as a natural component; roof-level bonding of every metallic penetration; SPD coordination at incoming, distribution and terminal levels.

Authority step: Staged utility and Civil Defence inspections, third-party LPS verification report, and inclusion of the earthing/LPS test regime in the building O&M and annual FM programme.

Industrial, warehouse and logistics

Earthing arrangement: TN-S with dedicated earths for process plant, and separate functional/static earthing where flammable materials are handled.

Electrode: Ring earth plus rod array; segregated earth for hazardous-area static bonding points and tank farms.

Bonding scope: Racking, cranes and gantries, dock levellers, conveyors, silos, fuel and chemical tanks, LPG installations, filling points and static bonding reels, welding bays and battery-charging areas.

Lightning protection: IEC 62305 with explicit attention to hazardous zones — the LPS design must address side-flash and equipotential bonding into any classified area.

Authority step: Utility acceptance plus Civil Defence and, where applicable, environmental/industrial-licensing inspection of static and hazardous-area earthing.

Temporary construction supply

Earthing arrangement: TT with RCDs, or generator-derived earthing; PME/TN-C-S earths are not to be relied on for a temporary site supply unless every extraneous part is reliably bonded.

Electrode: Dedicated site earth rods at each generator, transformer and main distribution assembly, tested before energisation and re-tested at defined intervals.

Bonding scope: Generator frames, site accommodation, hoarding, scaffolding, tower crane, hoists, site steel, welding return paths, fuel tanks and any metalwork that could become live.

Lightning protection: Temporary tall structures — tower cranes, hoists, masts — need an earthing arrangement and a documented lightning/high-wind stand-down procedure.

Authority step: Utility temporary supply approval; ADOSH-SF CoP 15.0 (Abu Dhabi) / DM requirements for temporary electrical installations; competent-person inspection before energisation and at each move.

Hazards & controls

What actually hurts people on this task

No person enters the bore, ever

A 6–10 m earth bore cannot be self-rescued from and cannot be safely entered for retrieval. Cover or rigidly barricade it whenever drilling stops, including breaks.

Underground service strike while augering

Earth pits are usually located in landscape strips and near the plot boundary — exactly where LV cables, irrigation, telecom and district cooling run.

  • Utility drawings and NOCs obtained and on site; validity dates checked
  • CAT/genny and GPR scan by a competent locator, marked up and re-scanned after any delay
  • Hand-dig or vacuum-excavate the first 1.2 m or through the service zone, whichever is deeper
  • No mechanical drilling inside the utility owner's tolerance zone until positively proved
  • Stop-and-reassess trigger written into the permit for any unknown service, void or backfill
Auger entanglement, rotating attachment and crush

A rotating auger will pull in clothing, gloves, lanyards and hands faster than a person can react, and the excavator slew zone overlaps the working area.

  • Barriered exclusion zone at maximum boom and attachment reach plus a margin
  • Nobody within the zone while the auger is rotating or raised; positive signal protocol with a trained banksman
  • OEM-compatible attachment only; quick-coupler engagement, pins, locks, guards and hoses verified at every pre-start
  • No loose clothing, no gloves that can be drawn in near the rotating element, no manual guiding of the auger
Open bore left unattended

A 6–10 m open bore is a fall-and-entrapment hazard and cannot be self-rescued from.

  • Rigid cover or barricade fitted whenever drilling stops, including breaks and shift end
  • Bore never entered by any person for any reason
  • Spoil set back from the bore edge and kept clear of access routes
Exothermic welding — molten metal, fire and burns

Exothermic (thermite-type) connections reach very high temperatures, eject sparks and can ignite dry vegetation, packaging or fuel vapour.

  • Hot work permit where the project regime requires it; fire watch and extinguisher at the connection point
  • Dry mould, correct cartridge size, manufacturer procedure followed; damp moulds cause explosive ejection
  • Face shield, leather gauntlets, flame-resistant clothing; bystanders excluded
  • Combustibles cleared; post-work fire watch before the area is left
Earth pit and inspection chamber entry

A deep or covered inspection pit can accumulate gases, water and heat and may meet the confined-space definition.

  • Classify the pit before entry; gas test and permit where the confined-space definition is met
  • Cross-reference the confined space entry procedure and rescue arrangement
  • Cover control and edge protection while the pit is open
Step and touch potential during testing and faults

Injecting test current, or an earth fault while conductors are disconnected, can raise dangerous potentials at the electrode and along the ground surface.

  • Testing by an authorised competent person only, with the installation dead or under an approved live-test procedure
  • Test leads routed and marked; public and other trades kept clear of the test spread
  • Never disconnect the main earthing conductor of a live installation without a documented temporary bonding arrangement
Live LV work at the main earthing terminal

The MET is inside an energised meter or LV room; arc flash and contact with live parts are the fatal risks at final connection.

  • Isolation and LOTO with proving dead before work at the board
  • Authorised electrician only; arc-rated PPE and insulated tools where live proximity is unavoidable
  • Access to the utility room only with the supply authority's permission where the room is under their control
Manual handling, lifting rods and heat

Sectional rods, mould kits and pit covers are awkward and heavy, and the work is outdoors during the UAE heat season.

  • Mechanical aids for pit covers and rod handling; two-person lifts defined in the task brief
  • Midday break rule applied in season; shaded rest point, cool water and acclimatisation for new workers
  • Cross-reference the heat stress and welfare operating model
Corrosion, theft and later degradation

Saline and sabkha soils attack connections, and exposed copper tape and pit covers are routinely stolen from occupied buildings.

  • Copper-bonded electrodes and approved corrosion-resistant connections; no dissimilar-metal joints in soil
  • Tamper-resistant labelled pit covers; earth tape protected in accessible areas
  • Periodic re-test interval and visual inspection written into the O&M and FM planned-maintenance system

Verification

The test regime that gets you energised

Every test below is performed by an authorised competent person with calibrated instruments and recorded on the supply authority's certificate format.

TestMethodWhenNote
Soil resistivityWenner four-pin array at the electrode location, several spacings and directions.Design stage, before the electrode schedule is fixed.Record season and moisture condition — dry-season values govern the design.
Earth electrode resistanceFall-of-potential (three-pin/62% method) with the electrode disconnected, or clamp-on method on an interconnected system.After installation, before backfill sign-off, and again at handover.Use the acceptance value stated in the approved design and the supply authority's requirement; do not apply a generic value copied from another project.
Continuity of protective and bonding conductorsLow-resistance ohmmeter (R1+R2 or long-lead method) on every protective and bonding conductor.Initial verification and after any alteration.Includes every main bond identified on the bonding schedule, not a sample.
Insulation resistance500 V DC (or as specified) between live conductors and earth, with sensitive equipment disconnected.Before energisation.Record the disconnected equipment list with the certificate.
Earth fault loop impedance (Ze and Zs)Loop impedance tester at origin and at the furthest point of each final circuit.Before energisation and at periodic inspection.Compare against the maximum permitted for the protective device and disconnection time.
RCD operationRamp and trip-time tests at rated and multiplied residual current, plus the test button.Before energisation, then at the periodic interval in the O&M.Essential where the installation relies on a TT arrangement.
LPS continuity and SPD verificationContinuity across down conductors and test joints; SPD status indication and coordination check against the design.At LPS completion and at the periodic interval in IEC 62305 / the maintenance plan.The LPS earth and the electrical earth must be bonded as designed — an isolated LPS earth is a hazard, not a safeguard.

Acceptance values come from the approved design and the supply authority — not from a generic figure. Record the measured value with the method, instrument, calibration date and season.

Authorities & emirates

Who inspects and who energises

Three separate approvals typically apply: the supply authority for the earthing and wiring, Civil Defence for fire-system bonding and the lightning protection interface, and the municipality or free-zone regulator for the construction-phase works.

Dubai

Supply authority
DEWA — supply authority, internal wiring inspection, energisation and metering.
Wiring / installation rules
DEWA Regulations for Electrical Installations, applied together with the Dubai Building Code and the consultant's IEC 60364-based design. Free-zone plots (Trakhees/PCFC, DDA, DAFZA, JAFZA) apply their own permit and inspection route on top of the utility requirements.
Fire & life safety
UAE Fire and Life Safety Code of Practice, enforced by Dubai Civil Defence — covers bonding and earthing of fire pumps, alarm and detection systems, and lightning protection interface.
Construction HSE framework
Dubai Municipality Code of Construction Safety Practice and the Health & Safety Technical Guidelines (including TG 137 risk assessment and TG 38 heat stress) for the construction-phase works.
Notes
Confirm whether Dubai Municipality or a free-zone regulator such as Trakhees is the authority having jurisdiction before the permit is issued — the more stringent requirement governs.

Abu Dhabi

Supply authority
ADDC (Abu Dhabi) / AADC (Al Ain) under the Abu Dhabi Department of Energy; TRANSCO for transmission-level interfaces.
Wiring / installation rules
Abu Dhabi DoE Electricity Wiring Regulations (IEC 60364 based), plus Abu Dhabi International Building Code and Estidama where applicable.
Fire & life safety
UAE Fire and Life Safety Code enforced by Abu Dhabi Civil Defence (ADCDA).
Construction HSE framework
ADOSH-SF (formerly OSHAD) — CoP 15.0 Electrical Safety, CoP 29.0 Excavation Work, CoP 39.0 Overhead and Underground Services, CoP 36.0 Plant and Equipment.
Notes
Musanada/ADM and master developers may impose additional inspection hold points on infrastructure and community plots.

Sharjah

Supply authority
SEWA — supply, inspection and energisation.
Wiring / installation rules
SEWA electrical installation requirements with Sharjah Municipality building approvals.
Fire & life safety
UAE Fire and Life Safety Code enforced by Sharjah Civil Defence.
Construction HSE framework
Sharjah Municipality construction safety requirements; Sharjah Prevention and Safety Authority for high-risk and emergency matters.
Notes
Industrial areas frequently require additional static and hazardous-area earthing evidence at inspection.

Ajman

Supply authority
Ajman Sewerage / FEWA-successor EtihadWE for electricity supply in served areas.
Wiring / installation rules
EtihadWE installation requirements with Ajman Municipality permits.
Fire & life safety
UAE Fire and Life Safety Code enforced by Ajman Civil Defence.
Construction HSE framework
Ajman Municipality & Planning Department construction HSE conditions.
Notes
Free zone plots (AFZA) route inspections through the free-zone engineering office.

Umm Al Quwain

Supply authority
EtihadWE.
Wiring / installation rules
EtihadWE installation requirements with UAQ Municipality approval.
Fire & life safety
UAE Fire and Life Safety Code enforced by UAQ Civil Defence.
Construction HSE framework
UAQ Municipality construction permit conditions.
Notes
Allow additional lead time for utility witness testing outside the main urban area.

Ras Al Khaimah

Supply authority
RAK Electricity & Water Authority (RAKEWA) / EtihadWE depending on the area.
Wiring / installation rules
RAK Municipality building and electrical approval route; RAKEZ for free-zone industrial plots.
Fire & life safety
UAE Fire and Life Safety Code enforced by RAK Civil Defence.
Construction HSE framework
RAK Municipality construction safety requirements.
Notes
Rocky and mountainous ground in parts of RAK often forces deep-bore or enhanced electrodes — resistivity survey early.

Fujairah

Supply authority
EtihadWE.
Wiring / installation rules
EtihadWE installation requirements with Fujairah Municipality approval.
Fire & life safety
UAE Fire and Life Safety Code enforced by Fujairah Civil Defence.
Construction HSE framework
Fujairah Municipality construction permit conditions.
Notes
High-resistivity rock and coastal salt exposure both apply — specify corrosion-resistant connections and re-test intervals accordingly.

Standards commonly cited

ReferenceWhat it covers
IEC 60364-5-54Earthing arrangements, protective conductors and protective bonding conductors — sizing and installation.
IEC 60364-4-41Protection against electric shock; automatic disconnection of supply, disconnection times, RCD requirements.
IEC 60364-6Initial and periodic verification — the test sequence and certification content.
IEC 60364-7-701 / -702 / -712Special locations: bathrooms, swimming pools and fountains, PV systems.
BS 7430Code of practice for protective earthing of electrical installations — electrode design, soil resistivity, measurement methods.
IEC 62305-1 to -4Lightning protection: general principles, risk management, physical damage/LPS, and protection of electrical and electronic systems (SPD coordination).
IEC/BS EN 62561 seriesLPS components — connection, conductor, earth electrode, test joint and SPD component requirements.
IEC 61643 seriesSurge protective devices for low-voltage power and signal systems.
IEEE 80 / IEEE 81Substation grounding (step and touch potential) and field measurement of earth resistance and resistivity.
DEWA Regulations for Electrical InstallationsDubai supply authority requirements for earthing, bonding, inspection and energisation.
Abu Dhabi DoE Electricity Wiring RegulationsAbu Dhabi wiring, earthing arrangement and inspection requirements.
UAE Fire and Life Safety Code of PracticeBonding and earthing of fire systems, lightning protection interface, and Civil Defence inspection.
ADOSH-SF CoP 15.0 / 29.0 / 39.0Abu Dhabi occupational requirements for electrical safety, excavation work, and overhead and underground services.
Dubai Municipality Technical Guideline 137Health and safety risk assessment format expected with the method statement.

Gap review

What an earth-pit drilling MSRA usually leaves out

A method statement written around the excavator and auger covers roughly the first third of the task. These are the items to add before the document is approved for a live installation.

GapAdd to the MSRA
Supply-authority wiring regulations not citedName the governing utility (DEWA / ADDC / AADC / SEWA / EtihadWE / RAKEWA) and its electrical installation regulations as the primary technical reference for the earthing arrangement, inspection and energisation.
No soil resistivity survey stepAdd a Wenner resistivity survey as a design input and a hold point before the electrode schedule and bore depth are confirmed.
Electrode-to-installation connection not coveredExtend the scope through the earthing conductor route, the inspection pit, the main earthing terminal and the protective bonding schedule — the drilling is only the first third of the task.
Exothermic welding treated as an excluded activity with no alternativeEither include an exothermic-connection procedure with hot work permit, fire watch and PPE, or specify an approved mechanical clamp and state that thermite connections require a separate permit.
Lightning protection interface absentState whether the electrode forms part of an IEC 62305 LPS or a common earthing system, and who verifies the bond between LPS and electrical earth.
Surge protection and equipotential bonding not referencedReference SPD installation and equipotential bonding at services entry, so the earthing submittal, the LPS design and the SPD schedule are consistent.
Civil Defence interface missingAdd the UAE Fire and Life Safety Code interface — bonding and earthing of fire pumps, alarm panels and firefighting risers is inspected by Civil Defence, not the utility.
Inspection pit classified only as a small excavationAdd a confined-space classification test for the inspection chamber, with gas testing and rescue arrangements where the definition is met.
Step and touch potential during testing not assessedAdd a testing section covering test-spread control, keeping others clear, and the prohibition on disconnecting a live installation's main earthing conductor without temporary bonding.
No acceptance criteria or test certificate listList the tests, the instruments, the calibration requirement and the approved acceptance value, and attach the utility's certificate format.
Corrosion and material compatibility not specifiedSpecify copper-bonded electrodes, approved connection types and a prohibition on dissimilar-metal joints and improvised backfill additives in saline or sabkha ground.
Environmental controls not addressedAdd spoil management, drilling-fluid and slurry control, hydrocarbon spill kit, and disposal of enhancement compound packaging per the project environmental plan.
Temporary-to-permanent earthing changeover not plannedDefine how the temporary construction earthing is removed and the permanent system taken into service, with a record of the changeover.
Handover and periodic re-test not definedAdd as-built pit locations, labelled covers, O&M content and the periodic re-test interval passed to the facilities-management team.
Third-party and adjacent-property risk not coveredWhere the pit is near a boundary, public footpath or occupied unit, add public-interface barriers, signage and out-of-hours security of the open bore.

FAQ

Earthing questions we get asked

Who approves the earthing system for a villa in the UAE?

The supply authority for the emirate — DEWA in Dubai, ADDC or AADC in Abu Dhabi and Al Ain, SEWA in Sharjah, EtihadWE or RAKEWA in the Northern Emirates. They inspect the internal wiring and earthing arrangement and energise the meter. The consultant signs the design and test records, and Civil Defence inspects the fire-system bonding where fire systems are installed. In a free zone or master-planned community, the free-zone regulator or master developer adds its own NOC on top.

Do I need a permit to drill an earth pit?

Yes — it is a ground-disturbance activity. You need the project excavation/ground-disturbance permit, the utility drawings and NOCs for the location, and a competent scan and marking before mechanical drilling. Treat every unverified service as live and hand-dig or vacuum-excavate through the service zone first.

What earth resistance value do I have to achieve?

Use the value in the approved design and the supply authority's requirement for the installation type. Values quoted in general reference books are not an acceptance criterion, and a value copied from a previous project is the most common cause of a rejected test. Record the dry-season measured value with the method and instrument calibration.

Does a townhouse cluster need an earth rod per unit?

Normally not. The usual arrangement is an interconnected earthing network per block or substation, with each unit's main earthing terminal bonded back into it. Isolated rods per unit can create potential differences between adjacent units. Follow the approved distribution design.

When is lightning protection required?

It follows an IEC 62305-2 risk assessment rather than a fixed building height. Towers, commercial buildings, industrial plants with hazardous materials, and buildings with rooftop PV, masts or exposed plant will normally require an LPS. The LPS earth is bonded to the electrical earthing system as designed; leaving them separate creates a dangerous potential difference during a strike.

Can the same earth be used for the electrical system, lightning protection and IT equipment?

Modern practice is a single, common bonded earthing system with dedicated earth bars for sensitive equipment referenced back to the main earthing terminal — not separate isolated earths. Where a clean or technical earth is specified for IT or medical equipment, it is still bonded at the MET; the separation is in the routing, not in the reference.

How often should the earthing be re-tested after handover?

The re-test interval belongs in the O&M manual and the facilities-management planned-maintenance system, set from the periodic verification requirements of the design standard and the authority's requirement for the building type. Saline, coastal and sabkha ground justifies a shorter interval because connections corrode faster.