Electrical authorities & standards

Back to Site Electrical

Electrical authorities & standards

Temporary site power is regulated by the supply authority of the emirate you are building in, layered with OSH requirements and international wiring standards. Last updated 2 August 2026.

By emirate

Federal (All UAE)

Ministry of Human Resources & Emiratisation / UAE Cabinet (MoHRE / Federal)

No single federal electrical code for construction sites. All emirates follow their own authority regulations built on IEC 60364 and BS 7671 principles. ADOSH-SF CoP 15.0 applies federally for OSH purposes.

Abu Dhabi

Abu Dhabi Department of Energy (DoE) / ADDC / ADOSH-SF (ADPHC) (DoE / ADDC / ADOSH-SF)

Abu Dhabi's DoE EWR 2020 is based on IEC 60364 and governs all low-voltage electrical installations. ADDC (Abu Dhabi Distribution Company) conducts inspections and energisation approvals. ADOSH-SF CoP 15.0 covers occupational electrical safety on construction sites. Temporary installations are covered under Section 9.6 of EWR 2020.

Dubai

Dubai Electricity and Water Authority (DEWA) / Dubai Municipality (DEWA / Dubai Municipality)

Dubai follows the Dubai Building Code (2021) which supersedes the DEWA 2017 Regulations. General assemblies for distribution of electricity on construction sites must conform to BS 4363 and BS EN 61439. DEWA approves temporary power connections for construction purposes. The Dubai Municipality Code of Construction Safety Practice covers site electrical safety obligations.

Sharjah

Sharjah Electricity, Water & Gas Authority (SEWA) / OSHJ (SPSA) (SEWA / OSHJ)

Sharjah follows federal MoHRE standards supplemented by SEWA connection requirements. OSHJ (Occupational Safety and Health in Sharjah) enforces site electrical safety under the ADOSH-SF framework adapted for Sharjah. All installations must comply with the UAE Fire and Life Safety Code.

Ras Al Khaimah

RAK Electricity / RAKEZ / Etihad Water and Electricity (EtihadWE) (EtihadWE / RAKEZ)

RAK follows federal MoHRE and ADOSH-SF standards. EtihadWE (formerly FEWA) provides power supply and connection approvals for the northern emirates including RAK. RAKEZ industrial zones have additional electrical safety requirements for managed worker accommodation.

Ajman / Fujairah / UAQ

Etihad Water and Electricity (EtihadWE) / Local Municipalities (EtihadWE / Municipalities)

Ajman, Fujairah, and Umm Al Quwain follow federal MoHRE standards and EtihadWE connection requirements. Local municipality building departments oversee electrical installation approvals. All installations must comply with IEC 60364 / BS 7671 principles as adopted in the UAE.

Free Zones

Trakhees (JAFZA/Dubai Free Zones) / RAKEZ / KIZAD / Other FZAs (Trakhees / FZAs)

Each free zone authority may impose supplementary electrical requirements. Trakhees enforces the UAE Fire and Life Safety Code and Dubai Building Code for JAFZA and other Dubai free zones. KIZAD (Abu Dhabi) follows DoE EWR 2020. RAKEZ follows its own managed industrial zone standards.

Standards & legal instruments

ReferenceTitleAuthorityScope / notes
DoE EWR 2020Abu Dhabi Electricity Wiring Regulations 2020Abu Dhabi DoEAll LV installations in Abu Dhabi — based on IEC 60364
ADOSH-SF CoP 15.0Electrical Safety Code of Practice v4.0 (July 2024)ADPHC / ADOSH-SFOSH electrical safety — all construction sites UAE-wide
Dubai Building Code 2021Dubai Building Code — Electrical Engineering WorksDubai Municipality / DEWAAll electrical installations in Dubai — supersedes DEWA 2017
DEWA 2017DEWA Regulations for Electrical Installations (2017)DEWADubai — superseded by DBC 2021 but still referenced for temporary supplies
DM CCSPDubai Municipality Code of Construction Safety PracticeDubai MunicipalityCovers electrical safety obligations on Dubai construction sites including temporary installations, inspection requirements, and contractor responsibilities.
BS 4363:1998Distribution Assemblies for Reduced Low Voltage Electricity Supplies for Construction and Building SitesBSIMandatory reference standard for all temporary site distribution boards in the UAE. Specifies construction, IP rating, socket types, and safety requirements for site DBs.
BS EN 61439-4Low-Voltage Switchgear and Controlgear Assemblies — Part 4: Particular Requirements for Assemblies for Construction SitesBSI / IECConstruction site DBs — required by DoE EWR 2020 and DBC 2021
IEC 60364 seriesLow-Voltage Electrical InstallationsIECFoundation international standard series. Abu Dhabi DoE EWR 2020 is based on IEC 60364. Key parts: 4-41 (protection against electric shock), 4-43 (overcurrent protection), 5-52 (wiring systems), 5-54 (earthing), 6 (verification), 7-704 (construction sites).
IEC 60446Basic and Safety Principles for Man-Machine Interface — Identification of Conductors by Colours or AlphanumericsIECMandatory colour coding for all UAE electrical installations
IEC 61008Residual Current Operated Circuit-Breakers Without Integral Overcurrent ProtectionIECGoverns RCD performance requirements including trip current and trip time. 30 mA RCDs must trip within 40 ms at rated current.
UAE Fire & Life Safety CodeUAE Fire and Life Safety Code of PracticeCivil Defense / Ministry of InteriorFire safety, fuel storage, emergency lighting — all emirates
NFPA 70EStandard for Electrical Safety in the WorkplaceNFPA (USA)Not a UAE regulatory requirement but widely referenced by multinational contractors for arc flash assessment, PPE requirements, and electrical safety management systems on UAE industrial sites.